====== Eaton 5p 850i ====== ===== Batterietausch zurücksetzen ===== - Ensure the UPS is plugged in and powered with the batteries connected, but that the UPS output is off (it will be in a shutdown state with no power to the load) - Make note of any settings you changed/configured in the UPS - Navigate to Control > Restore Factory Setting, then click "Yes" if it asks, "Are you Sure?" - Once the factory reset is performed, unplug the UPS and wait until the display goes completely dark and the fans turn off. - Plug the UPS back in to the wall/source, configure any appropriate settings, then power on the UPS. - Wait approx. 1 minute, then verify the alarm is no longer active/no red LED and no alarms on the web card. - If you have a network card, under "UPS Status," hover your mouse over the battery symbol. The info box to the side should show a date of "49 months" or similar for the "Life Time" to further verify the LCM reset has taken place.